Siemens controls technical resource
SINAMICS G120 F30001 overcurrent fault stopped the motor?
F30001 reports power-unit overcurrent. It does not identify a failed inverter or tell you whether the event began with the motor circuit, control configuration, supply, or load. The point in the cycle where the first fault occurred is often more discriminating than the presence of the code alone.
Read the first trip against the operating phase
Siemens lists motor/cable short or ground fault, control parameterization and other conditions for F30001 in the CU240B-2/CU240E-2 list manual. A trip before shaft movement, during acceleration and only after load engages calls for different comparison of existing records. The manual also defines the phase/DC-link bits of r0949 for its documented variant; a bit identifies where overcurrent was recognized, not what caused it.
Operators can note the first displayed message and whether the motor had begun moving. Electrical testing, fault-value interpretation against the installed variant and any parameter comparison belong to qualified personnel with site authorization; do not cycle the fault or touch motor wiring.
A trip coded F30002 belongs to the DC-link overvoltage investigation, not this overcurrent branch.
Siemens official technical reference — use the edition and hardware scope stated by Siemens; this is background for interpreting evidence, not a diagnosis of a particular machine.
What F30001 tells you—and what it does not
Siemens' G120 CU240B-2/CU240E-2 list manual identifies F30001 as “Power unit: Overcurrent” and describes several possible causes. Confirm the installed Control Unit, Power Module and firmware before using a manual for a particular variant. The separate F07801 motor-overcurrent message is not interchangeable with F30001.
Trips at start or while accelerating
Was it before motion, on the up-ramp, or once the load engaged? Siemens lists a motor or power cable short-circuit or ground fault, incorrect control parameterization, and—in U/f operation—a too-short up-ramp among possible causes. Timing frames a comparison; it does not make any one of these the cause.
Only under load or after a supply event
Compare the first trip with the normal cycle and any documented motor, cable or supply change. Siemens also lists high post-charging current after a voltage dip, a line phase interrupted, and power-unit damage as possibilities. A line event and a loaded motor call for different evidence, not an automatic inverter replacement.
What the fault value can locate
For the cited CU240B/E-2 manual, r0949 is a bitwise binary indication: bit 0 is phase U, bit 1 is phase V, bit 2 is phase W, and bit 3 indicates overcurrent in the DC link. A value of 0 means the affected phase was not recognized. The fault value does not identify the root cause or authorize work on energized equipment; preserve it only if already available.
Onsite diagnostic goal: compare event timing, existing drive diagnostics, motor/load context and authorized electrical evidence to narrow the fault area—not promise a restart or a replacement part.
Optional details if already available
Call first if the machine has stopped. The following can help a qualified investigation when safely known; do not delay a request for service to collect them.
- Machine location, affected motor and last successful operation.
- Photo of F30001, its fault value and the first other alarms, if already displayed.
- Whether it trips before motion, while accelerating, under load or after a recent equipment change.
- G120 Control Unit and Power Module order numbers, if already known, plus drawings and an unmodified project backup.
Is this the right fault guide?
F30002 during deceleration points to a different DC-link overvoltage investigation. If the display instead reads F01910, follow the fieldbus setpoint-timeout guide. With no confirmed code or no start command, begin with the G120 won't-start guide; if the whole machine's stop source is unknown, use the machine-down overview.