Siemens PLC in RUN but the machine won't start?

RUN says the controller is executing its program; it does not certify that the machine is ready. A start may be refused before an output is requested, or a sequence may begin and then stop on an input, interlock or drive state. Those are distinct observations.

Locate the last accepted stage of the sequence

The S7-1200 manual describes RUN as execution of the user program, not a verdict on application permissives. Compare the operator start request, application state, output command and the receiving device status in that order using existing records. If the command never appears, a motor fault is not yet established; if it appears but the drive reports a fault, investigate the receiver separately.

Operators can observe the screen and whether any normal motion began. Monitoring live tags or interpreting permissive logic requires a qualified person with authorization and a matching project; never force an output or defeat an interlock to prove a path.

If CPU status is actually STOP, use the controller STOP investigation rather than this application-in-RUN path.

Siemens official technical reference — use the edition and hardware scope stated by Siemens; this is background for interpreting evidence, not a diagnosis of a particular machine.

RUN is controller status, not a machine-ready verdict

Siemens describes RUN as the mode in which an S7-1200 executes its user program. That does not establish that an operator start request was accepted, that the required conditions for a particular sequence are met, or that an output and its field device have responded. Those questions depend on the machine's actual design. See Siemens' S7-1200 program-execution documentation.

PLC shows RUN; start does nothing

Record what the operator requested, which mode was selected and whether the HMI displayed a message. A start request, an operating-mode selection, or a machine-specific permissive may be missing; the CPU's RUN indication alone cannot distinguish them.

A sequence begins, then stops

Note the last completed action and what was expected next. An output command, device response, sensor feedback or sequence condition may need investigation. Do not assume the component nearest the stop point is faulty.

HMI message or drive fault appears

Preserve the exact alarm text and order of events. A message may name a blocking condition, a communication problem or a downstream symptom; it is evidence to compare with the machine state, not a complete diagnosis.

Different symptom? If the CPU actually reports STOP, the S7-1200 CPU STOP / PROFIBUS diagnostic record shows a logged configuration event with a STOP transition, not a confirmed machine all-stop. It cannot explain a machine whose PLC remains in RUN.

What an onsite investigation can compare

The objective is to locate the first condition that differs from the intended sequence, not to guess a replacement part from a single alarm. Depending on the installed equipment, documentation and authorized access, the investigation may compare:

  • Operator request and machine state: Is the requested operating mode available? What happens on the HMI, and at what step does progress stop?
  • PLC and I/O evidence: What status, diagnostic buffer entries and device indications are available near the time of the event? Siemens documents the S7-1200 diagnostic buffer as a record of recent CPU events; an empty or unrelated entry does not prove that the machine sequence is healthy.
  • Sequence conditions: An authorized controls professional can trace the start request through relevant machine-specific permissives, interlocks, commands and feedback in the actual project. Siemens' TIA Portal watch-table documentation describes online monitoring of tag values; those values need to be interpreted against the installed program and machine state.
  • Drive or field-device response: If a command is expected, distinguish a missing command from a displayed drive fault, unavailable device or missing feedback before concluding where the fault lies.

These are possible diagnostic areas, not a claim that any particular permissive, sensor, drive or network has failed. Online monitoring and configuration access depend on site authorization and the available engineering project. This page is not a procedure for changing safety logic or restarting a stopped machine.

Existing observations, if available

Share what operators and maintenance staff can already observe, if available:

  • Machine location, machine name, affected station or axis, and whether the problem is constant or intermittent.
  • The observed PLC RUN/STOP indication, what operating mode was selected, the operator action requested, and the last machine action that completed.
  • Exact HMI messages and drive fault or warning codes, with photos of existing displays and the approximate order and time they appeared.
  • Whether any part still operates as previously observed; report existing observations rather than operating equipment just to reproduce the fault.
  • Recent changes, power events or prior troubleshooting attempts, plus available drawings, machine documentation and an unmodified project backup if the site has one.
  • A site contact who can authorize access and provide the PLC, HMI and drive models if already known. Do not open a panel merely to obtain a model number.

Related Siemens troubleshooting paths

If the CPU status or initiating fault is still unknown, start with the Siemens machine-down diagnostic guide, which covers PLC, HMI and drive evidence together. If the issue centers on an axis that jumps or faults as it is commanded, the SINAMICS S120 positioning-axis case documents a different, case-specific drive investigation.

If the machine requests motion but a SINAMICS G120 drive will not start or displays a fault, see the G120 drive-start guide for drive-side evidence to gather; first establish whether the drive actually received a request.

If a saw shuttle specifically reports that its reference point is not set after power-up and automatic cutting remains unavailable, the saw shuttle reference guide separates a missing position reference from a general PLC-in-RUN start problem and a separate servo fault.

If the PLC remains in RUN while a PROFINET I/O station is reported not reachable, the PROFINET device-offline guide covers the station and network evidence to gather before attributing the stop to PLC logic.

If the operator panel cannot communicate with the PLC or its values appear stale, start with the HMI-to-PLC communication guide rather than treating the HMI message as proof that a start request reached the controller.

If an S7-1500 controller actually enters STOP, use the S7-1500 CPU STOP guide to preserve the CPU event sequence instead of following this PLC-in-RUN start path.

Scope of service: An onsite visit is for troubleshooting, diagnostics and fault identification to help determine the next action. Findings depend on access and the evidence available; a restart, part replacement or equipment repair is not promised.