Siemens axis jumps or faults immediately: a SINAMICS S120 case
This sanitized case describes unexpected positioning-axis behavior on an S120 drive system, with A07496 and A07441 observed during investigation. Its documented correction was specific to that configuration; it is not a homing or download recipe for another machine.
Why the two alarms must not be merged
The case record distinguishes the A07496 enable indication from A07441 encoder-adjustment status. The former was interpreted with its alarm value and valid actual-position feedback; the latter was a separate status observed in the same investigation. Comparing the drive data set and online configuration was case work, not proof that every jump has the same cause. Siemens S120 alarm definitions must be matched to the installed firmware before generalization.
An operator should keep clear of unexpected axis motion and preserve already-visible messages only. Qualified drive personnel can compare the correct project, feedback status and alarm values under site motion and hazardous-energy procedures; do not jog or reload the axis to reproduce the case.
F07900 is a different motor-blocked/speed-limit fault path.
Siemens official technical reference — use the edition and hardware scope stated by Siemens; this is background for interpreting evidence, not a diagnosis of a particular machine.
What an operator may notice without Siemens software
From the machine side, the problem may look like an axis that jumps when asked to operate, will not move, faults immediately, or cannot complete a positioning move. Those observations are useful even if the HMI does not display a Siemens drive alarm number.
If already visible, record the operator message, what the machine was commanded to do, which axis was involved, and whether the issue began after a configuration or commissioning change. These are clues, not proof that the encoder or motor itself has failed.
What the drive diagnostics showed
The positioning drive objects included HEAD_POSITION and LENGTH_STOP on a SINAMICS S120 / CU320-2 DP system. The investigation involved drive configuration, encoder and position feedback, DDS configuration, and a comparison of online drive information.
A07496: EPOS: Enable not possible
In this case, alarm value (2) indicated that the valid actual-position feedback signal was missing. That diagnostic signal did not, by itself, prove a failed physical encoder.
A07441: encoder adjustment status
A07441 was also present. The absolute encoder adjustment status had changed, and the position offset needed to be saved nonvolatile. This was part of the diagnostic picture, not a claim that it alone caused the axis behavior.
Configuration comparison
The team compared online drive information with the drive configuration and examined DDS and position-feedback settings rather than treating the displayed alarm as a complete diagnosis.
A07496 can have different underlying causes. Its alarm value and the installed drive configuration matter; DDS reconfiguration is not a universal fix for A07496.
A07496 pointed to missing valid actual-position feedback in this record; A07441 described a changed encoder adjustment status. Neither message alone identified the faulty setting. Comparing the online configuration and DDS provided a separate line of evidence before the case-specific correction.
What resolved this particular configuration issue
In this confirmed case, the corrective sequence was to load the configuration from the drive to the PG, reconfigure the DDS correctly, and load the corrected configuration back to the drive. The configuration issue was resolved, allowing further progress toward commissioning and getting the machine into production. The record does not confirm a completed motion test or production run.
Case-specific result, not a general procedure: The outcome applies to this drive/positioning configuration issue. Do not copy a configuration, change DDS, or enable an axis based on an alarm code alone. Such work requires a qualified person, the actual machine documentation, site authorization, and appropriate safety controls.
For other machine-stop symptoms, see our Siemens machine-down diagnostic guide. A separate S7-1200 / CM 1243-5 TIA Portal migration case concerns PLC/PROFIBUS project compile errors, not this S120 axis fault.
For a different drive-start problem involving a SINAMICS G120 that will not run or shows a fault, see our G120 drive-start diagnostic guide. The S120 positioning configuration found in this case is not a diagnosis for a G120.
For a different controller diagnostic record, an S7-1200 buffer logs I/O access errors, a station event and a later hardware-configuration event with STOP. Its machine outcome is unconfirmed. The S7-1200 I/O-station event record is distinct from this S120 positioning-axis misconfiguration.
A different S120 axis fault
If the drive instead displays F07900 motor blocked / speed controller at its limit, see the S120 F07900 diagnostic guide. The A07496 finding in this case does not identify the cause of a different fault code.